How Does a Marx Impulse Generator Work?

A Marx generator charges several capacitors in parallel and discharges them in series through spark gaps, so that the output voltage is approximately the sum of the charging voltages of each stage.

The idea

Obtaining an impulse of hundreds of kilovolts from a DC source of moderate voltage would require an enormous source. The Marx generator solves this with a trick: each stage is charged to a modest voltage and the stages are then suddenly connected in series.

Charging phase

Each stage has a capacitor and a spark gap, that is, two electrodes separated by air. The stages are linked by charging resistors. A DC voltage source charges all the capacitors in parallel, each to the source voltage. The spark gaps do not conduct because the electrode spacing is sufficient for that voltage.

Discharge phase

When breakdown is triggered in the first spark gap, the voltage across the next gap exceeds its breakdown level, so it also breaks down, and so on in a cascade. When all the gaps are conducting, the capacitors are in series and the output voltage is on the order of the number of stages multiplied by the charging voltage, somewhat less because of losses. The charging resistors limit the current in this phase so that it does not escape through the source.

How the wave is shaped

  • A front resistor in series with the output, together with the capacitance of the test object, determines how quickly the voltage rises.
  • A tail resistor, in parallel, determines how quickly it decays.
  • Changing these resistors makes it possible to obtain lightning impulses, which are fast, or switching impulses, which are slower.

What the engineer sees in practice

Firing is controlled with an auxiliary trigger spark gap or by adjusting the electrode spacing. The actual waveform depends on the load: each test object requires the circuit to be readjusted. The voltage is measured with a divider, not taken from the charging voltage.

These activities involve hazardous voltages: they must be carried out by qualified, authorized personnel, following the applicable regulations and the facility’s lockout and grounding procedures.