24/7 emergencies 814 777 6921812 230 6079WhatsApp 811 786 0768
Electrónica MonterreyElectrónica MonterreyLaboratorios Creativeit Talk to an engineer
Menu

How Is the Lightning Impulse Waveform Measured?

The waveform of a lightning impulse is measured with a voltage divider and a high-speed recorder, and is characterized by its front time, its time to half-value and its overshoot.

What a standard lightning impulse is

It is a voltage that rises very quickly to a peak and then decays slowly, with a shape that imitates, in simplified form, the effect of a lightning stroke. The standard shape is described as 1.2/50 µs: approximately 1.2 µs of front and 50 µs until the voltage falls to half the peak.

The measuring chain

  1. Voltage divider, normally of the capacitive or resistive-capacitive type, which reduces the voltage to a measurable level while preserving the waveform.
  2. Coaxial cable with matched termination, to avoid reflections that would deform the signal.
  3. Digitizer or oscilloscope with sufficient bandwidth and sampling rate for a front in the microsecond range.

What parameters are extracted

  • Peak value: the amplitude of the test. When there are oscillations at the crest, the test value is defined with a standardized filtering procedure.
  • Front time: calculated from two points on the rising edge, not from the origin, because the actual start is difficult to locate.
  • Time to half-value: from the virtual origin until the tail falls to half the peak.
  • Overshoot: the excess of the crest over the base value, caused by circuit inductances.

How to adjust the result

The shape depends on the generator and on the capacitance of the test object. A highly capacitive load lengthens the front; a highly inductive load, such as a transformer, shortens the tail time. The front and tail resistors are adjusted until the shape falls within the tolerances of the test standard.

Sources of error

The measuring system must be calibrated and verified against a reference system. Long ground connections, coupling and a divider with a slow response distort the shape. Consult the current edition of the standard on high-voltage test techniques.

These activities involve hazardous voltages: they must be carried out by qualified, authorized personnel, following the applicable regulations and the facility’s lockout and grounding procedures.

We do real tests, on video! Watch them on our YouTube channel →

Do you have a problem nobody has been able to measure?

Talk directly to the engineer in charge, with no middlemen.

Talk to an engineer