How Is Leakage Current Measured During a DC Test?

Leakage current in a DC test is measured with a microammeter at the source and interpreted by separating capacitive charging, absorption and conduction, the component that reveals the condition of the insulation.

What the current is made of

When DC voltage is applied, the current is not constant. First there is a capacitive charging current, which decays very quickly. Next comes an absorption current, which decays more slowly because of dielectric polarization. What finally remains is an almost steady conduction current, which is the leakage current proper. Surface leakage over terminals or insulators adds to it.

How it is measured

  • The meter, a microammeter, is built into the test set or inserted in the return path.
  • If the test object has dirty surfaces, it is useful to measure with the guard so that surface current is not recorded.
  • It is advisable to wait for the current to stabilize before taking the reference reading, rather than reading immediately.

The voltage step technique

Instead of applying a single value, the voltage is raised in steps, waiting the same time at each one and noting the current. In healthy insulation, the current increases roughly in proportion to the voltage. If the curve bends upward, with current rising faster than voltage, a defect is becoming conductive; this is the signal to stop the test before breakdown.

How to interpret the result

  • Low, stable current: insulation in good condition.
  • High current from the start: moisture or contamination.
  • Current rising over time at constant voltage: deterioration in progress.
  • Unstable readings with jumps: possible discharges at terminals or in air; check clearances and surfaces.

The current depends on temperature and on the length of the test object, so it is compared with previous tests on the same item.

When finished, discharge and ground the test object before handling it.

These activities involve hazardous voltages: they must be carried out by qualified, authorized personnel, following the applicable regulations and the facility’s lockout and grounding procedures.