How Is the Insulation Resistance of a Motor Measured?

The insulation resistance of a motor is measured with the motor de-energized and disconnected from its supply cable, by applying DC voltage between the windings and the grounded frame.

What is measured

The test evaluates the insulation between the stator coils and the frame, which is grounded, and sometimes between phases. A motor in good condition shows high, rising insulation resistance; moisture, conductive dust and thermal deterioration reduce it.

General procedure

  1. De-energize, lock out and verify the absence of voltage. If the motor has just stopped, it is hot and may retain charge.
  2. Disconnect the supply cables in the terminal box. Otherwise the cable, the starter and the connected equipment are measured as well.
  3. Connect the instruments: line terminal to the winding and ground terminal to the frame. With the three windings tied together, the entire stator is measured at once; with them separated, testing each phase with the others grounded makes it possible to locate the problem.
  4. Select the voltage suited to the motor’s rated voltage, according to the applicable procedure.
  5. Apply the voltage and record the reading at defined times, often at one minute and at ten minutes to obtain the polarization index.
  6. Discharge the winding by keeping it grounded before touching it.

How to interpret the result

  • A reading that is low from the start suggests moisture or contamination.
  • A reading that rises over time is a sign of dry, healthy insulation; the polarization index measures that rise.
  • A reading that falls during the test may signal a localized fault.

Record the winding temperature and apply a correction in order to compare with previous tests. In motors that are several years old, the trend matters more than the absolute value.

What to check first

If the value is low, first check whether the cables were still connected and whether there is moisture in the terminal box. Then consider cleaning and drying before reaching a decision on the condition of the winding.

These activities involve hazardous voltages: they must be carried out by qualified, authorized personnel, following the applicable regulations and the facility’s lockout and grounding procedures.