What Are Creepage Distance and Clearance?

Creepage distance is the shortest path along the surface of the insulator between two conductive parts; clearance is the shortest path through the air. The first controls tracking and the second controls sparkover.

Two distances, two phenomena

Between two conductive parts at different voltages there are two possible paths for a fault. One crosses the air in a more or less straight line. The other follows the surface of the insulating material that separates them.

Clearance Creepage distance
Definition Shortest distance between the two conductive parts, measured through the air Shortest distance between them, measured along the surface of the insulator
Risk it controls Disruptive discharge in air due to overvoltage Leakage currents, tracking and surface flashover
Depends mainly on Maximum voltage or expected overvoltages, altitude Continuous service voltage, contamination, material

Why they are not the same

Creepage distance is always equal to or greater than clearance, because the surface follows contours, ribs or sheds that lengthen the path. This is why outdoor insulators have sheds: they increase the creepage distance without lengthening the insulator, and they protect part of the surface from rain.

What determines them

  • Clearance: it is defined from the transient overvoltages that must be withstood. Altitude affects it, because less dense air withstands less field and more separation is required.
  • Creepage distance: it is chosen according to the continuous voltage, the contamination level of the environment and the tracking properties of the material. A saline or industrial environment demands more creepage. Materials with better tracking resistance allow smaller distances, depending on the standard.

An example

In a switchboard, two bars separated by an insulator can meet the clearance requirement and still fail through tracking if the surface path is short and the environment is damp and dusty. This is corrected by lengthening the path with a barrier or a rib.

When they do not hold up on their own

A nominal distance is not enough if contamination, condensation or wear reduce it in practice. Product and installation standards set the minimum values according to voltage, overvoltage category, pollution degree and material, and must be consulted in their current edition.

Warning: designing and verifying distances in high-voltage equipment is the responsibility of qualified personnel, in accordance with applicable regulations.