24/7 emergencies 814 777 6921812 230 6079WhatsApp 811 786 0768
Electrónica MonterreyElectrónica MonterreyLaboratorios Creativeit Talk to an engineer
Menu

What Is a Disruptive Discharge?

A disruptive discharge is the sudden collapse of the insulating capability between two electrodes, when a complete conductive channel forms between them; gases and liquids usually recover, while a solid is left with permanent damage.

Definition

An insulator withstands voltage as long as it does not conduct. A disruptive discharge occurs when, under a sufficiently high field, a continuous conductive channel forms joining the two electrodes, the voltage falls almost to zero and a current flows that is limited only by the external circuit. Unlike a partial discharge, which bridges only part of the gap, a disruptive discharge crosses it completely.

What it is called depending on where it occurs

  • Spark or arc in air (or in gas): the discharge passes through the gaseous medium. When the gas recovers, the insulation is restored.
  • Flashover: the discharge travels along the surface of a solid insulator, such as an insulator string, through the air next to its surface. The insulator may remain intact, though marked.
  • Puncture: the discharge passes through the interior of a solid insulator. The channel is left carbonized or melted, and the damage is irreversible.
  • Breakdown in a liquid: the discharge passes through an insulating oil; it leaves decomposition products and carbon particles, although the liquid recovers part of its dielectric strength.

Why it occurs

It happens because the field exceeds the dielectric strength of the medium at some point, and the discharge propagates quickly as an ionization avalanche until the channel closes. The probability depends on the voltage waveform, the geometry, impurities and the conditions of the medium, such as humidity, pressure or contamination. A lightning or switching overvoltage can cause it even when the normal operating voltage does not.

What the engineer sees

  • Protection trips from ground-fault or phase-to-phase fault current.
  • Burn marks on surfaces, punctures in insulators or oil containing carbon.
  • A sudden voltage drop during a test, with a rise in current, which activates the test set’s protections.

How to interpret the result

In a dielectric test, a disruptive discharge indicates that the insulation did not withstand the applied voltage. In service, finding the path makes it possible to identify the cause: contamination, a defect, an overvoltage or inadequate design.

Warning: testing and working in installations where a disruptive discharge can occur involve a risk of death. This work must be performed by qualified personnel, in accordance with applicable regulations.

We do real tests, on video! Watch them on our YouTube channel →

Do you have a problem nobody has been able to measure?

Talk directly to the engineer in charge, with no middlemen.

Talk to an engineer