What Is the Corona Effect?

The corona effect is a localized electrical discharge in the air surrounding a conductor or a sharp point when the field at its surface exceeds what the air can withstand, without reaching a complete failure.

What happens

On a high-voltage conductor, the electric field is strongest at its surface, and stronger still at points, edges and broken strands. If the field in that zone exceeds the value the air can withstand, the air ionizes in that region only, and a continuous or intermittent discharge occurs. The gap between the electrodes keeps insulating, which is why this is called a partial discharge in air and not a complete arc.

What promotes it

  • High voltage relative to the geometry.
  • Small radii of curvature: points, burrs, sharp edges, unshielded bolts and fasteners.
  • Rough or contaminated surface, including water droplets on the conductor.
  • Low air density: at higher altitude, air withstands less field.
  • Humidity and rain: these increase activity on surfaces.

What is observed

  • A crackling or hissing sound.
  • Faint bluish or violet light, visible in the dark, and ultraviolet emission that can be detected with special cameras.
  • A smell of ozone.
  • Radio and television interference.
  • Energy loss, which increases in bad weather.

Why it matters

Besides losses and noise, corona produces ozone and nitrogen compounds that attack nearby materials such as elastomers and polymers, and it can damage insulation if it occurs on it. Intense activity on an insulator accelerates its deterioration and can precede surface failures.

How it is reduced

  1. Use larger-diameter conductors or several conductors per phase.
  2. Install equipotential rings and shields at ends and on hardware.
  3. Avoid points and edges: round them off, polish them, shield the fasteners.
  4. Keep surfaces clean.
  5. Increase the distances between elements at different voltages.

An example

An inspection with an ultraviolet camera detects activity on a piece of hardware on an insulator string. It is corrected with a ring or by replacing the damaged part, and checked again under similar conditions.

Warning: inspection of energized high-voltage installations must be done by qualified personnel, observing safe distances and applicable regulations.