Definition
Temperature is not uniform in a winding. The oil heats up as it rises, so the upper part is hotter; in addition, the conductor temperature exceeds that of the surrounding oil by the gradient imposed by heat dissipation. The combination of both effects, plus the local distribution of losses and oil flow, produces a zone of maximum temperature: the hot spot.
What it is made up of
- Ambient temperature.
- Top-oil rise over ambient.
- Gradient between the top oil and the conductor at the hottest point, which includes a factor representing the effect of local flow.
The sum of these terms gives the hot-spot temperature.
Why it governs
Insulation paper degrades at a rate that depends on temperature and increases rapidly with it. The hottest zone is therefore the one that ages first and that determines the service life of the insulation. It is also the place where, at very high temperatures, gas bubbles can form and reduce the dielectric strength.
How it is obtained
- Calculation: with the temperature rise test data and the thermal model equations in the loading guides.
- Thermal image: the winding temperature indicator estimates the value by adding a gradient proportional to the current.
- Direct measurement: with fiber-optic probes installed in the winding during manufacture, at the positions where the maximum is expected.
How to interpret the result
A high measured or estimated value, sustained over time, means accelerated aging. What matters is the combination of level and duration, not a brief peak. If the hot spot measured with fiber optics differs from the thermal-image estimate, it is advisable to check the indicator’s calibration.
When it does not apply
The model equations assume a unit in good condition, with normal oil circulation. If there are obstructions, cooling failures or internal faults, the actual hot spot may be higher than calculated.