What must be met
When two transformers are connected in parallel, both share the same buses on the primary and the secondary. Any difference between them shows up as circulating current or as a load sharing other than the one intended.
Conditions
- Same rated voltages on primary and secondary, and therefore equal turns ratios at the operating position. A difference produces circulating current even at no load.
- Same phase displacement or vector group. Two transformers with a different phase displacement between primary and secondary cannot be tied together, because the voltage difference between equivalent terminals would be very large.
- Same phase sequence and same polarity, so that each phase connects to its counterpart.
- Similar percent impedances, referred to each unit’s own rated power, so that each one takes load in proportion to its capacity.
- Reasonable power ratio, because a large difference usually comes with differences in impedance and short-circuit capability.
How the load is shared
Current divides in inverse proportion to impedance. With equal percent impedances, the sharing is proportional to the rated powers. If one impedance is lower, that transformer takes more relative load and may reach its limit before the other. The tap changer position also changes the ratio and the impedance, and must be coordinated between the two units.
Checks before closing
- Compare nameplates: voltages, vector group, impedance and tap in use.
- Confirm with turns ratio and vector group tests.
- Verify the phase sequence with a suitable indicator.
- With one unit energized and the other connected on the primary side only, measure the voltage between equivalent secondary terminals before closing the breaker: it must be practically zero.
An example
If two units of equal power are paralleled and one has a noticeably lower impedance, more current will flow through it. The sharing becomes unbalanced and that unit reaches full load first. The combined capacity is less than the sum of the nameplates.
Warning: phasing checks and closing breakers at medium and high voltage must be performed by qualified personnel, following applicable regulations and procedures.