A guide, not a code or a specification
Unlike a factory test code, this guide is intended for on-site work: acceptance, maintenance, fault location and evaluation after events. Its value lies in showing which test answers which suspicion and how to read the result, not in setting purchase criteria.
Types of tests it brings together
- Insulation: insulation resistance, power factor or tan delta, and capacitance of windings and bushings.
- Windings and core: winding resistance, transformation ratio, excitation current and leakage reactance.
- Mechanical integrity: frequency response (SFRA).
- Fluid: oil analysis and dissolved gas analysis.
- Accessories and tap changer: specific tests of bushings and the mechanism.
- Others: partial discharge, thermography and vibration, as the case requires.
How it is used in practice
- The reason is defined: commissioning, scheduled maintenance or investigation of a fault.
- The set of tests that answers that reason is chosen, not all of them by default.
- They are performed with attention to temperature, bushing cleanliness, core condition and connection configuration.
- They are interpreted by comparison with factory data, earlier tests, sister phases and similar units.
How to interpret the result
An isolated value says little. The guide insists on comparison and on combining tests: a rise in tan delta accompanied by moisture in the oil tells a different story from the same rise with dry oil. A single test rarely confirms a diagnosis.
When it does not apply
It does not replace factory tests or the manufacturer’s judgment. Nor does it cover all types of equipment, and some aspects, such as numerical criteria, depend on the type of unit and its history.
It is updated over time, so the current edition should be consulted. This guide describes only its general scope.
Warning: field tests on transformers involve electrical risk. They must be carried out by qualified personnel, following the applicable regulations and procedures.