Two ways of building the same magnetic path
The core carries the magnetic flux and is made of thin electrical steel laminations, insulated from one another to limit eddy currents. These laminations are usually grain-oriented, which carries flux better in the rolling direction. What distinguishes the two types is how the laminations are arranged.
Stacked core
Laminations are cut into strips with angled ends and stacked in layers, overlapping the joints of one layer with those of the next (staggered joints). The coils are placed on the limbs before the yokes are closed, or else the cores are assembled and the coils are inserted from the end. This is the usual solution in power transformers and large units.
Wound core
A continuous steel strip is wound on itself to form the magnetic circuit. With no joints along most of the path, the flux follows the favorable grain direction more closely. This tends to reduce excitation current, no-load losses and noise. It is widely used in distribution transformers of moderate size.
What changes in practice
- Joints: each joint introduces a small air gap that raises the excitation current. A wound core minimizes this effect.
- Manufacturing: a wound core requires ways of fitting the coils, either winding them directly onto the core or opening the strip and closing it again; on large units, this becomes difficult.
- Scalability: a stacked core adapts to a wide variety of sizes and geometries, including multi-limb cores.
- Mechanical stress: cutting and handling the lamination can degrade its magnetic properties; the manufacturing process matters as much as the type.
When the comparison does not apply
Each manufacturer designs according to its own process, and final losses depend on the steel, the design flux density and the quality of assembly, not just on geometry. Neither type should be assumed to be better in itself: the valid comparison is between specific designs with their loss data.