24/7 emergencies 814 777 6921812 230 6079WhatsApp 811 786 0768
Electrónica MonterreyElectrónica MonterreyLaboratorios Creativeit Talk to an engineer
Menu

How is residual core magnetization measured?

The core retains part of the magnetic flux after a disconnection or a direct current test; it is estimated by injecting controlled direct current and integrating the induced voltage, and it is removed by demagnetization.

Why the core stays magnetized

Core steel is a ferromagnetic material with hysteresis. When the magnetizing current is interrupted, the flux does not return to zero: a remanent flux remains, its value depending on the point in the cycle at which the disconnection occurred. A transformer disconnection, a nearby fault or a direct current resistance test can leave it magnetized.

What the engineer sees in practice

  • Higher inrush current on energization, because the remanent flux adds to the flux of the first half-cycle and pushes the core toward saturation.
  • Distorted excitation current, or excitation current that is asymmetrical between phases, in field tests.
  • Sweep frequency response (SFRA) results that differ from the reference in the low-frequency region, which depends on the magnetic state of the core.

How it is measured

There is no direct meter for the flux inside the core. The usual method is indirect: low-voltage direct current is applied to the winding and the voltage induced in another winding or in the same one is integrated over time. Because the voltage is the derivative of the flux linkage, its integral gives the change in flux. Driving the core to saturation in both directions provides references, and from them the remanent value is estimated. Commercial instruments are designed for this, and they also perform demagnetization.

Demagnetization

The general procedure applies direct current that reverses polarity with decreasing amplitude, so that the core goes through smaller and smaller hysteresis loops until it is left with minimal remanent flux. Some instruments do this automatically and verify the result.

When it matters

  1. Before tests that are sensitive to the state of the core, such as excitation current and SFRA.
  2. After direct current tests, such as winding resistance.
  3. Before re-energizing a large unit after a trip, to reduce inrush current.

It is advisable to define the order of the tests: those that use direct current should come after those that depend on a core in a neutral state, or else the core should be demagnetized between them.

Warning: switching operations on power transformers involve electrical risk. They must be carried out by qualified personnel, in accordance with the applicable regulations and procedures.

We do real tests, on video! Watch them on our YouTube channel →

Do you have a problem nobody has been able to measure?

Talk directly to the engineer in charge, with no middlemen.

Talk to an engineer