Where the noise comes from
The main noise of a transformer comes from the core. As it is magnetized, the steel changes dimensions slightly, an effect called magnetostriction, which occurs at twice the grid frequency and at its harmonics. On a sixty hertz grid, the dominant hum is at one hundred twenty hertz. Added to this is the noise of the cooling system fans and pumps and, under load, the noise of vibrations in the windings and structures.
What is measured
The sound pressure level, in A-weighted decibels, which approximates the sensitivity of the human ear. In some cases the sound power is also determined, with surface measurements or sound intensity measurements, which are independent of the surroundings.
General procedure
- The transformer is energized at rated voltage and rated frequency, in the condition defined by the procedure, with or without the fans running.
- A measurement contour is defined around the unit, at a specified distance from the main radiating surfaces and at a defined height.
- Measurements are taken at points spread along the contour with a sound level meter of the required accuracy class, verified with an acoustic calibrator before and after.
- Background noise is measured with the transformer de-energized, if possible, and the result is corrected for that contribution when the difference allows it.
- The results from the points are averaged on an energy basis, not arithmetically.
Conditions that affect the measurement
- Nearby reflective surfaces, such as walls or other equipment, which raise the level relative to the free field.
- Wind, rain, and noise from traffic or other equipment.
- Voltage: an increase in voltage raises the flux and the noise.
- The position of the microphone and the orientation of the sound level meter.
How to interpret the result
The measured value is compared with the manufacturer’s guarantee and with the limits that apply at the site, such as environmental noise limits for the area. A level higher than expected, or a changing tone, may be due to saturation, high voltage, loose parts, structural resonances or defective fans. To reduce it, acoustic enclosures, damped bases or barrier walls are used. Measurements near energized equipment must be made by qualified personnel, respecting safety distances.