24/7 emergencies 814 777 6921812 230 6079WhatsApp 811 786 0768
Electrónica MonterreyElectrónica MonterreyLaboratorios Creativeit Talk to an engineer
Menu

How is a sweep frequency response analysis (SFRA) performed?

Sweep frequency response analysis (SFRA) injects a low-voltage, variable-frequency signal into one transformer terminal and measures the response at another, producing a fingerprint that is compared with references and reveals mechanical deformation.

Principle

At high frequency, a transformer looks like a network of distributed resistances, inductances and capacitances determined by the geometry of the core and windings. If anything moves or deforms, that network changes, and the response changes with it. SFRA sweeps a wide frequency range and records the ratio of the output signal to the input signal, in magnitude and phase.

Measurement configurations

  • End-to-end with the other end open: the signal is injected at one end of the winding and measured at the other, for each phase.
  • End-to-end with the secondary winding short-circuited: reduces the influence of the core and highlights the windings.
  • Capacitive and inductive interwinding: these measure the coupling between windings.

What to watch when performing the test

The quality of the connection determines the quality of the measurement. Ground leads must be short and firmly attached to the terminal and to the tank ground; a poor connection distorts the high frequencies above all. The measurement cables must be those specified for the instrument. Connections must be repeated in the same way in every test campaign, with the tap changer in the same position, and the core must be demagnetized if the transformer has been subjected to direct current, because remanent magnetism affects the low frequencies.

How it is interpreted

The comparison can be made in three ways: against an earlier measurement of the same unit, against a sister unit, or against the other phases. The first is the most reliable; the second and third depend on comparable construction. The bands of the spectrum are generally associated with parts of the transformer:

  • Low frequencies: the core and its magnetization.
  • Medium frequencies: interaction between windings.
  • High frequencies: individual windings, connections and test leads.

A shift in resonances, the appearance of new ones, or a loss of similarity between like phases indicates a change. Diagnosing the cause requires experience and other tests, such as capacitance, short-circuit impedance and excitation current.

When it is applied

As a baseline at commissioning, after transport, after a through-fault or a seismic event, and as part of diagnostic programs. It is performed by qualified personnel with the transformer de-energized and isolated.

We do real tests, on video! Watch them on our YouTube channel →

Do you have a problem nobody has been able to measure?

Talk directly to the engineer in charge, with no middlemen.

Talk to an engineer