Setup
The low-voltage winding is short-circuited with short connections of ample cross section, and the high-voltage winding is fed at reduced voltage. The voltage is adjusted until the current is an appreciable fraction of rated current, and voltage, current and power are recorded. Since the core flux is very low in this condition, the excitation current is negligible and the measurement reflects the windings.
What is calculated
- The impedance, by dividing the voltage by the current, and its value as a percentage of the transformer’s base impedance.
- Its resistive component, from the power, and its reactive component, which dominates and is the leakage reactance.
- The load losses, taken from the power and referred to the reference temperature.
Why connection quality matters
Since the impedance is small, the resistance of any poorly tightened test connection or thin jumper adds to it and alters the result, especially the resistive part and the losses. That is why short, heavy jumpers and clean connections are used.
Variants
The measurement can be made three-phase, with the entire three-phase unit fed at once, or phase by phase. In the field it is usually done at lower than rated voltage and current, and the result is scaled. It is also measured at different tap changer positions, because the impedance varies with position.
Common mistakes
- Short-circuiting with unsuitable conductors.
- Not referring the losses to the reference temperature.
- Comparing with the nameplate without considering the tap changer position.
- Measuring low power factor power with low-accuracy instruments.
How to interpret the result
The result is compared with the nameplate value and with previous measurements on the same unit. A noticeable variation from the reference, or a difference between phases that did not exist before, suggests deformation or displacement of the windings, for example after a through-fault. A small change is not always damage, but it justifies a comparison with frequency response analysis.
The test is performed by qualified personnel, with the transformer de-energized and isolated, since high currents are involved.