Why it is limited
The paper and oil insulation of a transformer degrades over time, and this degradation depends heavily on temperature. The aging rate grows exponentially with it: a small sustained increase shortens life considerably. That is why standards set temperature rise limits above a reference ambient.
Which temperatures are distinguished
- Top oil temperature: that of the oil at the top of the tank, where it comes out hottest.
- Average winding rise: normally obtained from the change in conductor resistance between cold and hot.
- Winding hot spot: the maximum local temperature, usually in the upper part of the winding, and the one that most determines aging. In most cases it is not measured directly; it is estimated, or measured with fiber optic probes installed at the factory.
What it depends on
The rise results from the balance between the heat produced by the losses and the heat the cooling system manages to remove. It therefore depends on the design of the windings, on the cooling medium and on its circulation, natural or forced. The final temperature is the rise plus the ambient temperature, so a hotter ambient leaves less margin. Altitude also has an effect, because less dense air cools less effectively.
What operating implies
A transformer can be loaded above its rated power for limited periods, but the hot-spot temperature rises and, with it, the consumption of life. The thermal inertia of the oil and windings means the temperature does not respond immediately. Conversely, a transformer with a light load or a cold ambient has thermal reserve.
What the engineer sees
Oil and winding temperature indicators, temperature alarms and trips, and automatic control of fans and pumps. A temperature rise that is not explained by the load or the ambient points to a problem with cooling, oil circulation or internal losses.
How to interpret the result
Limit values and overload criteria are defined in the product standards, which must be consulted in their current edition. What matters in the field is the trend, comparing temperature with load and ambient, and the relationship to the design values.