What it is in physical terms
The core steel magnetizes up to a point at which almost all of its magnetic domains are already aligned. Beyond that point, increasing the current barely increases the flux. In this region the material behaves as if it had become “air” from a magnetic standpoint, and the magnetizing inductance falls.
Why it happens
Flux is determined by the applied voltage divided by the frequency. That is why there are several causes:
- Sustained overvoltage on the winding.
- Low frequency at rated voltage, as with a generator or drive running far from its voltage-to-frequency ratio.
- DC component in the load or the network, which shifts the flux curve to one side.
- Residual flux at energization, which adds to the flux of the first cycle and can saturate the core in a single half cycle.
What effects it produces
- High, peaky excitation current that overheats the winding carrying it.
- Harmonics in the current and distortion of the network voltage.
- Stray flux that escapes from the core and heats structural parts, such as covers and clamping hardware.
- Increased noise and vibration.
- Possible misoperation of protection sensitive to harmonics or energizing currents.
What the engineer sees
In operation, a louder and harsher hum, a temperature rise not explained by the load, and current distortion in a power quality recording. During energization, an inrush current with one-sided peaks and a high second-harmonic content, characteristic of this phenomenon.
How it is prevented or mitigated
The transformer is designed to operate with a margin below its maximum flux; the voltage-to-frequency ratio is limited with suitable protection, and the presence of DC components is monitored. At energization, controlled closing is used, or the peaks are accepted with protection that recognizes them.
It should be distinguished from current transformer saturation: that occurs in instrument transformers and causes measurement errors, and it is a different phenomenon with the same physical basis.