What Is the Excitation Current of a Transformer?

Excitation current is the current a transformer draws from its source with the secondary open and at rated voltage; it creates the core flux and covers the core losses, and its waveform is not sinusoidal because the magnetic material is not linear.

Definition

When one winding is fed at rated voltage and the others are open, a very small current flows compared with rated current. This is the excitation current. It is the part of the current that is not due to the load.

What its components are

  • A magnetizing component, which establishes the flux in the core and is almost in quadrature with the voltage.
  • A loss component, in phase with the voltage, which supplies the power consumed by hysteresis and eddy currents.

Why it is not sinusoidal

The relationship between magnetic field and flux in steel is not linear: near the saturation region, much more current is needed for a small increase in flux. Since the flux itself is practically sinusoidal, the current that produces it is distorted and rich in harmonics, especially the third. This distortion is normal and explains part of the harmonic currents that appear on the network.

What depends on what

Excitation current grows more than proportionally with voltage as saturation approaches. It is also affected by residual magnetism in the core, by the tap changer position and, in three-phase transformers with a three-leg core, by geometry: the center leg has a shorter magnetic path and draws less current than the outer legs. That is why it is common to see a pattern of two similar phases and one lower phase.

What the engineer sees

In an excitation measurement, the three phases are compared with one another and with previous records. A value different from the expected pattern can be associated with shorted laminations, a problem with core grounding, shorted turns in a winding, or a faulty tap changer. Residual magnetism after DC tests also alters the reading, so the core is demagnetized or the measurement is made beforehand.

Difference from energizing current

It should not be confused with inrush current, which occurs for a few cycles on energization and can be many times rated current, depending on the residual flux and the instant of closing. Excitation current is a steady value in normal operation.

Measurements on transformers are performed by qualified personnel, with the equipment de-energized and isolated.