The principle
When alternating voltage is applied to the primary winding, a current flows that creates a varying magnetic flux in the core. That flux also passes through the secondary winding and induces a voltage in it. Since the same flux links both, the ratio between the voltages is approximately the ratio between their numbers of turns. With direct current the flux does not vary and there is no transformation.
What determines the flux
The flux in the core is set by the voltage applied to the primary and the frequency, not by the load. If the voltage rises or the frequency falls, the flux increases and the core approaches saturation. This relationship between voltage and frequency explains why a transformer designed for one frequency is not fed at a lower one without reducing its voltage.
What happens when the secondary is loaded
When the secondary feeds a load, its current tends to reduce the flux. The primary responds by drawing additional current that offsets this effect, so the ampere-turn balance is maintained. That is why the primary current follows the secondary current, in inverse proportion to the voltage ratio. In addition to the load current, the primary draws a small excitation current that creates the flux and covers the core losses.
Main parts
- Core: laminated electrical steel, with insulation between laminations to reduce eddy currents.
- Windings: copper or aluminum conductors with paper and oil insulation, or solid insulation in dry-type transformers.
- Insulation and cooling system: the oil insulates and carries heat to radiators or coolers, with natural or forced circulation.
- Tap changer: adjusts the turns ratio to compensate the voltage, de-energized or under load.
- Bushings, tank and accessories: connection to the outside, protection and monitoring.
What it loses and what limits it
A transformer is very efficient but not ideal: it has core losses, present whenever it is energized, and winding losses that grow with the load. Its load limit is set by the insulation temperature. It also has an internal impedance that causes voltage drop and limits short-circuit current.
What the engineer sees in practice
A hum at twice the line frequency, an oil temperature that follows the load, and voltage ratios that match the nameplate. Deviations such as an incorrect ratio, an abnormal excitation current or unexplained heating indicate problems in the core or windings.
Tests and switching on transformers that are energized or connected to the grid are reserved for qualified personnel, under the applicable safety regulations.