What Is a Busbar or Bus?

A busbar, or bus, is a rigid conductor or a set of them that gathers and distributes current among several circuits connected at the same electrical point; in network studies, “bus” also designates that node in the model.

Function

A busbar is the point where the incoming feeds and outgoing circuits of a switchboard or substation come together. It is made of copper or aluminum, in the form of a bar, profile or tube, and is supported by insulators. It allows several breakers to be connected at the same potential without multiplying cables.

Two uses of the same term

  • Physical: the bar installed in a switchboard, a switchgear cubicle or a busway.
  • In the model: in a load flow or short-circuit study, a bus is a network node where elements are connected. A bus in the model may correspond to a real busbar or to a less tangible junction point.

What is verified on a busbar

  • Continuous current: it depends on the cross section, material, shape, ventilation and connection temperature, just like the ampacity of a cable, with its own temperature rise criteria.
  • Short-circuit withstand: fault current generates forces between bars that grow with the square of the current, as well as brief heating. The supports and cross section are sized to withstand them.
  • Insulation and clearances: phase-to-phase and to ground, according to the voltage.
  • Joints: the splices between bars are the points most prone to heating due to poor contact.

Configurations

A single bus is the simplest, but a fault on it takes everything connected to it out of service. A sectionalized bus with a tie breaker allows one part to be isolated while the other stays in service, at the cost of more equipment and a more careful protection calculation. There are double-bus or ring schemes for installations where continuity is especially important.

What the engineer sees

Hot spots at joints during thermography, discoloration, noise or arc tracks from deteriorated insulation and, after a fault, deformation or displacement of the bars. In the system model, the short-circuit current at each bus is compared with the rating of the equipment connected to it.

Busbars operate energized and with high available energy; their inspection and maintenance are reserved for qualified personnel, with the equipment de-energized and the safety measures of the applicable regulations in place.