What the trip actually measures
A thermal-magnetic breaker responds to two phenomena: the heat accumulated by the current, which bends a bimetallic element, and an instantaneous magnetic peak. An electronic breaker measures the RMS current and compares it with adjustable curves. Both can act on conditions other than a high continuous load.
Most frequent causes
- Inrush currents: motors, transformers and power supplies with capacitors have energization peaks that, in an unfavorable combination, exceed the instantaneous threshold.
- Temperature: the thermal element is sensitive to heat. A heavily loaded or poorly ventilated panel, or one with heavily loaded adjacent breakers, causes tripping at currents below the rating.
- Loose connection: it heats the breaker from its own terminals and trips it even though the current is normal.
- Ground leakage: if the breaker has residual-current or ground-fault protection, the filters of drives and switched-mode power supplies produce leakage currents that make it operate.
- Harmonics: they increase the RMS value and the peak relative to what an instrument that assumes a pure sine wave measures; in neutrals, triplen harmonics add up.
- Incorrect setting: an electronic unit set too low or with a curve inappropriate for the load.
- Incipient fault: intermittent arcs or degraded insulation that produce brief current pulses.
- Aging: a breaker with many years or many operations may lose calibration.
What the engineer sees
The trip occurs at certain times, when a piece of equipment starts or on hot days. The breaker may be hot to the touch. Spot measurements show normal currents, which is why logging is needed.
What to check first
- Log current and voltage over several operating cycles, capturing peaks.
- Check the temperature of the breaker and the panel.
- Check the tightness and condition of the terminals with the equipment de-energized.
- Compare the settings with the load curve and with downstream coordination.
- Determine whether the trip is thermal, magnetic or ground-related, according to the breaker’s own indicator.
These measurements are made on energized equipment and are for qualified personnel.