General scope
IEEE 242, known as the Buff Book, is a recommended practice that brings together criteria for protecting the electrical systems of industrial plants and commercial buildings. It is neither a product standard nor a regulation: it offers engineering guidance on how to protect and how to coordinate.
What topics it addresses
- Protection fundamentals: objectives, protection zones and requirements for speed, sensitivity and selectivity.
- Fault current sources and their influence on equipment selection.
- Protective devices: fuses, low-voltage circuit breakers and relays.
- Component protection: cables, transformers, motors, generators, busbars and capacitors.
- System grounding considerations and their effect on ground-fault protection.
- Coordination through time-current curves.
The central idea: selectivity
When a fault occurs, only the nearest upstream device should operate, so that the rest of the installation stays energized. To achieve this, the operating curves of the devices in series are plotted on the same graph and it is verified that they do not cross within the range of possible currents. However, protection must at the same time be fast enough to limit damage and arc energy, so selectivity and speed sometimes conflict and call for a compromise.
What data it takes to apply it
Coordination starts from a short-circuit study that determines the maximum and minimum available currents, and from system data: single-line diagram, transformer and cable impedances, device characteristics and existing settings. Without that data, the settings are guesses.
How it looks in the field
If coordination is poor, a fault in a branch circuit trips the main breaker and leaves a much larger area out of service than necessary. If protection is slow, the equipment fails with severe damage. Both symptoms point to reviewing the settings and documentation.
As a recommended practice, its criteria must be adapted to each installation and consulted in its current edition. Setting and testing protection on energized equipment is carried out by qualified personnel.