24/7 emergencies 814 777 6921812 230 6079WhatsApp 811 786 0768
Electrónica MonterreyElectrónica MonterreyLaboratorios Creativeit Talk to an engineer
Menu

What Is NFPA 70B and What Is It For?

NFPA 70B is the standard on electrical equipment maintenance: it describes how to structure a preventive maintenance program, what to inspect and test, and what criteria to use in deciding the frequency.

What it is for

NFPA 70B deals with the maintenance of installed electrical equipment, on the premise that well-maintained equipment fails less often and fails less dangerously. Historically it was a recommended practice and it has evolved into a more demanding document, so its current edition should be consulted to find out its status and what requirements it contains.

What it proposes in general

  • A documented electrical preventive maintenance program, with defined responsibilities.
  • An equipment inventory and an assessment of its condition.
  • Inspection and test frequencies based on the condition, environment, criticality and history of the equipment, not just on the calendar.
  • Records that allow results to be compared over time.

How it relates to other standards

It is not an installation standard; that role is filled by installation codes. Nor does it replace the electrical testing specifications that define procedures and acceptance criteria. NFPA 70B is concerned with organizing the program and describing maintenance by equipment type: panels, circuit breakers, transformers, motors, cables, grounding systems and others. It is complemented by the standard on electrical safety in the workplace, which governs how to do the work safely.

What the engineer sees in practice

A compliant program shows up in last-service labels, inspection forms, thermography with comparison between phases and between cycles, circuit breaker testing, insulation resistance measurement and records of what was found. The condition of the equipment is classified, and that classification determines the next interval: equipment in poor condition is checked sooner; critical equipment, more often.

How to interpret the result

The trend matters more than an isolated value. Insulation that drops cycle after cycle, or a hot spot that grows at similar load, indicates deterioration even if it is still within limits. Maintaining without recording makes it impossible to see that trend.

Maintaining energized equipment or opening enclosures exposes workers to arc flash and shock hazards; it must be done by qualified personnel, under the applicable safety regulations and with the corresponding protective equipment.

We do real tests, on video! Watch them on our YouTube channel →

Do you have a problem nobody has been able to measure?

Talk directly to the engineer in charge, with no middlemen.

Talk to an engineer