What it does
Instruments and relays cannot be connected directly to medium voltage. The potential transformer, also called a voltage transformer, has a primary connected phase to phase or phase to ground, and a secondary with a reduced, standardized voltage. The transformation ratio is fixed, so the secondary voltage reproduces the primary voltage to scale, with a very small magnitude and angle error. It also electrically isolates the instruments from the system.
How it works
It is a transformer operating almost at no load: its burden is small and of high impedance, made up of the inputs of voltmeters, meters and relays. It works at practically constant flux, which is why the secondary voltage follows the primary voltage. It is built to maintain accuracy within a burden range, and its accuracy class indicates the maximum error in that range. There are different classes for metering and for protection.
Differences from the current transformer
- The potential transformer is connected in parallel with the system and stays almost at no load; short-circuiting its secondary causes a very high current and damage. For this reason it is protected with fuses or breakers on the secondary.
- The current transformer is connected in series, and its secondary must not be opened with current in the primary.
Practical aspects
- Polarity: it must be respected for directional functions and power metering to be correct.
- Primary fuses: they protect the system in the event of an internal transformer fault.
- Ferroresonance: the interaction between the transformer’s nonlinear inductance and the system capacitances can produce oscillations and overvoltages; it is mitigated with suitable loading or damping.
- Types for very high voltages: capacitive dividers are used, which reduce the voltage by means of capacitors and an intermediate transformer.
What the engineer sees
Measurement errors from excessive burden or reversed connection, operated fuses, or trips due to loss of the voltage signal. Inspection and testing, including ratio and polarity tests, must be carried out by qualified personnel, with the equipment out of service and following applicable regulations.