24/7 emergencies 814 777 6921812 230 6079WhatsApp 811 786 0768
Electrónica MonterreyElectrónica MonterreyLaboratorios Creativeit Talk to an engineer
Menu

What Is a Numerical Protection Relay?

A numerical protection relay is a microprocessor-based device that samples currents and voltages, converts them to numbers, calculates quantities and executes protection functions in software instead of through electromechanical mechanisms.

How it works

The system currents and voltages reach the relay from the secondaries of the instrument transformers, through input transformers that isolate and scale them. A filter removes the frequencies that cannot be sampled correctly, and an analog-to-digital converter takes samples of each signal. The microprocessor applies algorithms, such as the Fourier transform, to extract the magnitude and angle of the fundamental component and calculate the quantities each function needs.

What sets it apart from an electromechanical relay

  • Multiple functions in a single device: overcurrent, ground fault, voltage, frequency, differential, distance and others, depending on the model and the manufacturer’s license.
  • Configurable characteristics: curves, settings and logic are defined in software, and several setting groups can be held.
  • Recording: time-stamped events, oscillography of the current and voltage waveforms around the fault, and operation reports.
  • Self-monitoring: the relay supervises its own operation and raises an alarm if it detects an internal anomaly.
  • Communications: relays are integrated into supervision and control systems using standardized protocols.

Functions are identified by standardized device numbers. For example, 50 designates instantaneous overcurrent, 51 time overcurrent, 87 differential protection, 27 undervoltage and 59 overvoltage.

What the engineer sees

After a fault, the record makes it possible to reconstruct which function operated, at what current and how quickly, which helps analyze the cause and verify whether the coordination responded as expected. Programmable logic replaces auxiliary relays and wiring.

What must be looked after

  • Settings management: document and control changes, and keep a backup of the configuration.
  • Firmware updates in line with the manufacturer’s recommendations.
  • Communication security, because the device is on a network.
  • Periodic secondary injection tests to verify inputs, functions and outputs.

Testing and setting are carried out by qualified personnel, and opening the secondary circuit of a current transformer with load on the primary must be avoided.

We do real tests, on video! Watch them on our YouTube channel →

Do you have a problem nobody has been able to measure?

Talk directly to the engineer in charge, with no middlemen.

Talk to an engineer