How Is the Ohmic Contact Resistance of Power Circuit Breakers Measured?

The ohmic resistance of the contacts of a power circuit breaker is measured with a micro-ohmmeter that injects a high direct current and measures the voltage drop over four wires, with the breaker closed and de-energized.

What is being looked for

When the breaker is closed, current passes through the surfaces of its contacts. If those surfaces wear, oxidize or lose pressure, the contact resistance increases and with it the heating under load. The resistance is very small, so a dedicated low-resistance instrument is required.

How the measurement works

A micro-ohmmeter injects a relatively high direct current through the closed pole and measures the voltage drop between two points. The resistance is the voltage divided by the current. The four-wire or Kelvin method is used: one pair of conductors carries the current and a separate pair measures the voltage. In this way the resistance of the test leads and their clamps is not added to the measurement, which is essential when the value sought is so low.

Conditions and procedure

  1. With the breaker out of service, de-energized, locked out and grounded in accordance with the safety procedure.
  2. Place the current leads outside the voltage leads, and the voltage leads as close as possible to the pole terminals.
  3. With the breaker closed, inject the current and measure each pole separately.
  4. Repeat the measurement and verify that it is stable.
  5. Record the value, test current, temperature and breaker condition.

How to interpret

  • Compare the three poles with one another: a marked difference points to a pole with a problem.
  • Compare with the factory value or with previous measurements of the same breaker. The trend is more informative than an isolated value.
  • Consult the manufacturer’s criterion for the maximum allowable value.

Common mistakes

  • Measuring with poor test connections, which give unstable values.
  • Using an ordinary ohmmeter, whose current is insufficient to break through surface films and give a representative reading.
  • Not measuring at the same point each time.

Complements

This test is complemented by operating times, insulation resistance and mechanical inspection. Acceptance values must be taken from the equipment documentation. This work on power circuit breakers is carried out by qualified personnel in accordance with applicable regulations.