From failure to measurement
Predictive maintenance rests on one fact: many electrical failures are not instantaneous but are preceded by deterioration that shows up in some variable. That is why the plan starts from the failures and not from the instruments. The question is which failure you want to prevent and which signal comes before it.
Planning steps
- Classify criticality. Equipment is ranked by the effect its failure has on safety, production, and cost, and by how difficult it is to replace. Critical items receive closer monitoring.
- List the failure modes. For example, loose connections, insulation degradation, contact wear, partial discharges, or winding overheating.
- Match technique and variable. Thermography for hot spots, insulation resistance and its trend, dissolved gas analysis in transformer oil, partial discharges in medium voltage, motor current analysis, vibration, and power quality records.
- Define the reference state. A first measurement in good condition serves as a baseline for comparison.
- Set frequencies. They depend on how quickly deterioration progresses and on criticality: what evolves quickly needs more frequent measurements or continuous monitoring.
- Establish action criteria. Which values or trends trigger a work order, following manufacturer recommendations and applicable standards.
What makes it work
Trend over isolated value: a single reading says little, while the change between comparable measurements reveals deterioration. For that, measurements are taken under repeatable conditions, with similar load and temperature and with the same method, and everything is recorded in an orderly way.
What makes it fail
- Collecting data without anyone reviewing it or making decisions.
- Measuring what is easy rather than what anticipates real failures.
- Not feeding the failures that do occur back into the plan.
Scope
Predictive maintenance complements preventive and corrective maintenance; it does not replace them. Measurements on energized equipment or work at high voltage must be done by qualified personnel in accordance with the applicable regulations.