How is an inverse-time overcurrent relay set?

An inverse-time overcurrent relay is set by choosing the pickup current, the curve, and the time multiplier so that it operates quickly on heavy faults, ignores normal load, and coordinates with neighboring devices.

What “inverse time” means

In an inverse-time relay, the trip time decreases as the current increases. A moderate overload takes a while to trip and a short circuit trips almost immediately. This characteristic makes it possible to protect equipment while tolerating normal brief overloads and coordinating with devices in series.

The parameters that are set

  • Pickup current: the value from which the relay starts timing. It is seen through the current transformer ratio, so it must be converted between primary and secondary current.
  • Curve type: the standardized families, such as normal inverse, very inverse, or extremely inverse, differ in how quickly the time falls with current. A steeper curve makes it easier to coordinate with fuses or with devices that are also very inverse.
  • Time multiplier or time dial: shifts the curve up or down on the time axis.
  • Instantaneous element: a second function that trips without delay above a high threshold.

How the setting is reasoned

  1. Determine the maximum load current and normal transients: motor starting, transformer magnetization, load pickup after an interruption.
  2. Set the pickup above that current with a margin, and below the minimum fault current it must detect, according to the short-circuit study.
  3. Choose the curve compatible with that of the upstream and downstream devices.
  4. Adjust the multiplier so that the trip time leaves the coordination interval relative to the downstream device, at the maximum fault at which both see current.
  5. Place the instantaneous element above the maximum fault of the next device, if selectivity is required, or lower if speed takes priority.
  6. Verify that the curve lies below the damage curve of the protected equipment.

Verification

Settings are checked by injecting current on the secondary side and measuring the operating time against the curve. The secondary circuit of a current transformer must never be opened with current in the primary, because a dangerous voltage is generated. These tests are for qualified personnel following the applicable regulations.