How is voltage drop calculated in a feeder?

Feeder voltage drop is calculated by multiplying the current by the effective impedance of the conductor, which combines resistance and reactance with the power factor, and it is expressed as a percentage of nominal voltage.

The basic formula

For a three-phase circuit, the line voltage drop is approximated by the expression ΔV = √3 · I · L · (R·cos φ + X·sin φ), where I is the load current, L the conductor length, R and X the resistance and reactance per unit length, and φ the power factor angle. In a two-conductor single-phase circuit, the factor √3 is replaced by 2, because the current travels out and back. The result is then divided by the nominal voltage to obtain the percentage.

Why each term appears

The current produces a resistive drop in phase with it and a reactive drop leading it by 90 degrees. Only the part projected onto the voltage subtracts from the voltage at the load, which is where the cosine and sine terms come from. With low power factor loads, reactance carries more weight; in large cross-section conductors, reactance dominates over resistance.

Data that must be used correctly

  • Resistance: depends on the material, the cross-section, and the operating temperature. Using the value at the actual working temperature is more faithful than the value at room temperature.
  • Reactance: depends on the spacing between conductors and on whether the raceway is magnetic or not. It is taken from manufacturer tables or the standard.
  • Current: the operating current for normal service, and the starting current for the motor case.
  • Power factor: that of the load in operation; during starting it is low and different.

An example of the reasoning

If a long feeder supplies a motor, the drop is calculated first with the rated current and the full-load power factor. It is then repeated with the starting current and the low power factor typical of that moment, to confirm that the terminal voltage allows the motor to accelerate and that the contactors do not drop out.

How to interpret the result

The value is compared with the limits recommended by the applicable regulations for feeders and branch circuits, which should be consulted in their current edition. If it exceeds them, the cross-section is increased, the distance is shortened, the circuit voltage is raised, or the power factor is corrected. When several sections are in series, the drops add up. Installation and field verification are for qualified personnel.