What it solves
A load flow study answers this question: with these loads running and these sources available, what is the voltage at each bus, how much current and power flows through each conductor and transformer, and how much is lost? It is a calculation of normal, steady-state operation, not of faults.
How it is calculated
The power equations in a network are nonlinear, because power is the product of voltage and current. They are therefore solved with iterative methods, such as Newton-Raphson or Gauss-Seidel, which start from an estimate and correct it until the results agree with the data. For each bus, the program needs to know what is given: the power consumed, or the voltage and power in the case of a generator, plus a reference bus that absorbs the mismatch.
Input data
- Impedances of cables, lines, and transformers, and tap positions.
- Active and reactive power of the loads, and their power factor.
- Source data: voltage and available short-circuit power.
- Capacitors, reactors, and local generators.
Useful results
- Voltage profile: buses with out-of-range voltage at full load or minimum load.
- Loading of transformers and conductors relative to their capacity.
- System losses.
- Reactive power flow and power factor at the connection point.
What it is used for
It is used to evaluate expansions before connecting new loads, select transformer taps, locate capacitor banks, and understand where energy is being lost. It also makes it possible to study scenarios: operation with a transformer out of service, at full load, at minimum load, or with local generation.
How it differs from a short-circuit study
Load flow works with normal currents and voltages close to nominal. A short-circuit study calculates fault currents and uses a different model. Both use the same single-line diagram and the same impedance data. The quality of the result depends on the quality of the nameplate or measured data, so it is advisable to validate with measurements in the plant, made by qualified personnel.