What changes when a plant is connected
A distribution grid was designed for energy to flow from the substation to the loads. A distributed generation plant injects power at an intermediate point and modifies voltages, flows, and fault currents. The assessment examines each of these changes.
Aspects analyzed
- Voltage profile: when power is injected, the voltage at the connection point tends to rise, especially on long or high-impedance feeders with little load. It is verified that the voltage stays within the limits set by the applicable regulations.
- Reverse flow: if generation exceeds the local load, power flows toward the grid. Some regulation and protection equipment is intended for flow in one direction only.
- Protections: the plant contributes fault current, which can change the sensitivity and coordination of existing devices. Anti-islanding protection, which prevents the plant from continuing to supply a disconnected portion of the grid, is also reviewed.
- Waveform quality: inverters can contribute harmonics, and rapid variation of the source, as with solar under cloud cover, can cause voltage fluctuations or flicker.
- Stability and regulation: the effect on tap changers and capacitors on the grid.
Assessment method
- Model the local grid in load flow and short-circuit studies, with and without the plant and in maximum and minimum load scenarios.
- Measure before connection to obtain a baseline at the point of coupling.
- Measure after commissioning, over a period representative of generation and demand.
- Compare voltage, distortion, unbalance, and flicker against the applicable criteria.
- Verify the interconnection protection functions through testing.
How to read the results
The effect depends on the strength of the grid at the connection point: the higher the short-circuit power relative to the plant’s power, the smaller the disturbance. Each utility’s interconnection requirements and the regulations in force determine the acceptance criteria. Tests and switching at the interconnection are for qualified personnel.