Why does a variable frequency drive fail when the DC bus voltage drops?

A drive fails during a voltage drop because its inverter is fed from the DC bus, and when that bus falls below its minimum threshold the drive protects itself and trips on undervoltage.

The cause: the DC bus is the energy reservoir

In a drive, the rectifier bridge converts the AC input voltage into DC voltage, and the bus capacitors store it. The inverter draws from that bus the energy it delivers to the motor. If the grid suffers a sag, the rectifier stops conducting when the input voltage is lower than the bus voltage, and the capacitors must cover the load demand on their own. Because the motor keeps demanding power, the bus discharges and its voltage drops.

When the bus falls below the undervoltage threshold, the drive trips to avoid operating the inverter with insufficient voltage, which would produce higher currents for the same power and poor motor control.

What determines whether it trips

  • Drive load: the higher the power demanded, the faster the bus discharges.
  • Bus capacitance: determines how much energy it can supply during the sag.
  • Sag depth and duration: a deep, short sag may be tolerated; a moderate but long one may not.
  • Single-phase sag or unbalance: the rectifier keeps conducting partially, bus ripple increases, and the input current becomes more distorted.
  • Threshold and ride-through function settings: some drives can maintain control during the sag by using the kinetic energy of the load.

What the engineer sees in practice

The drive shows a bus undervoltage or phase-loss fault, sometimes without anyone noticing the event on the grid. At other times the trip occurs when the voltage recovers: the capacitors recharge with a high current, and an overcurrent fault may appear or an upstream protection may open. The drive’s fault log usually records the bus voltage at the moment of the trip.

How to diagnose it

  1. Review the drive’s fault history and note the date and time.
  2. Install a power quality analyzer at the drive input and record time-stamped events.
  3. Correlate the recorded sag with the trip.
  4. Determine whether the sag originates on the grid or inside the plant, for example from another motor starting or a fault on a neighboring circuit.

Possible measures

Depending on the cause, options to evaluate include using the drive’s own ride-through function for loss of grid power, adding input or bus inductance, providing energy backup on the bus or on the control supply, or correcting the origin of the sag. Any threshold adjustment must respect what the manufacturer allows. Work on an energized drive, whose capacitors retain charge after disconnection, is for qualified personnel following the applicable regulations.