The mechanism
A capacitor is capacitive at all frequencies, while the source, including the transformer and the line, is inductive. At a certain frequency, the two reactances become equal. Seen from the load, which injects harmonic currents, the capacitor and the source inductance are in parallel, and at that frequency the impedance of the combination is very high. A small harmonic current at that frequency produces a large harmonic voltage, and a current much larger than the injected one circulates through the internal capacitor-source circuit.
Where the resonant frequency falls
Approximately, the harmonic order of resonance is the square root of the short-circuit power at the point divided by the reactive power of the bank. A stronger grid, with high short-circuit power, shifts the resonance toward higher orders; a larger bank shifts it toward lower orders. If it falls close to a harmonic the load produces, such as the fifth or seventh with six-pulse rectifiers, the problem is serious. Because the bank’s power changes as steps are switched in, the resonance moves and the problem can be intermittent.
What an engineer sees in practice
- High voltage distortion at one specific harmonic.
- Capacitor current much higher than expected, overheating, or blown fuses.
- Drive or protection trips with no apparent cause.
- A spectrum with a clear peak that changes as different bank steps are operated.
How it is confirmed
The current and voltage spectra are measured with and without steps connected, and the grid impedance is calculated or simulated as a function of frequency. An impedance peak at the order of a harmonic that is present confirms the resonance.
What is done about it
The usual solution is to avoid the coincidence: change the size of the steps, use series reactors with the capacitors so that the combination is inductive at harmonic frequencies, or install tuned or active filters. There is also series resonance, in which the impedance is at a minimum and which is exploited in filters. Work on capacitor banks is for qualified personnel, following the applicable regulations.