The sum that does not cancel
In a three-phase, four-wire system with balanced, linear single-phase loads, the fundamental currents of the three phases are one hundred twenty degrees apart and their sum in the neutral is zero. But the third harmonic and its odd multiples (ninth, fifteenth) have the same angle in all three phases with respect to their own wave, meaning they are in phase with one another. These harmonics, called triplen or zero-sequence harmonics, do not cancel: they add arithmetically in the neutral conductor.
Why there are so many in buildings
The switch-mode power supplies of computers, office equipment, electronic lighting and chargers are single-phase loads with a rectifier and capacitor, rich in third harmonic. In buildings with many of them spread across the three phases, the neutral current can approach or exceed that of a phase, even when the phase currents are moderate.
Consequences
- Heating of the neutral conductor, which is often the same size as the phase conductor or smaller, and of its terminals and bars.
- Loose neutral connections that heat up further and can end up burned.
- Additional heating in transformers: triplen harmonics circulate in the delta winding and increase its losses.
- Elevated neutral-to-ground voltage and noise in sensitive equipment.
What an engineer sees in practice
The neutral is hotter than the phases on thermography, there is an odor or discoloration at terminals, and the phase circuit breakers show no overload. The key is to measure the neutral current with a true RMS instrument, since an average-responding meter markedly underestimates it with distorted waves. Spectral analysis is dominated by the third harmonic and its multiples.
How to interpret the result
If the measured neutral current exceeds what the conductor can carry, the options are to separate neutrals by circuit, increase the neutral size, use transformers designed for harmonic loads, or use filters that trap triplen harmonics. Measurements and modifications in energized panels must be carried out by qualified personnel, in accordance with applicable safety regulations.