Why do power factor correction capacitors heat up?

Power factor correction capacitors heat up because they absorb harmonic currents that add to the fundamental, because of overvoltage, because of resonance with the grid, or because of internal losses in an aged or poorly ventilated capacitor.

The most frequent cause: harmonics

A capacitor’s reactance decreases as frequency increases. For the harmonic currents of an installation, the capacitor is a low-impedance path, so it attracts those currents. Heating depends on the total RMS current flowing (fundamental plus harmonics) and on the dielectric losses. A capacitor designed for the fundamental current can be overloaded even though the reactive power looks correct.

Resonance

The capacitor forms a resonant circuit with the grid inductance. If the resonant frequency matches a harmonic that is present, the current in the capacitor is greatly amplified and heating is severe, with a risk of failure. It is one of the most dangerous causes of overload, and it can change when steps are switched in or out.

Other causes

  • Sustained overvoltage: capacitor power grows with the square of the voltage, and harmonic voltage adds to the peak voltage.
  • Poor ventilation or high ambient temperature, which reduce the ability to dissipate heat.
  • Aging: loss of capacitance from damaged elements unbalances the currents and overloads the remaining units.
  • Loose connections at terminals, which produce hot spots.
  • Frequent switching with high inrush currents.

What an engineer sees in practice

The signs are bulging cases, blown fuses, heating on thermography, abnormal noise or delivered reactive power below the rated value. An analyzer is used to measure the actual capacitor current and its harmonic content and compare them with the current allowed by the manufacturer. The capacitance of each unit is also checked.

What to check first

  1. Current and voltage harmonics at the bank’s panel.
  2. Possible resonance: does the problem change when steps are switched in or out?
  3. Operating voltage compared with the capacitor’s rated voltage.
  4. Condition of ventilation, connections and fuses.

Capacitors retain charge after being disconnected. They must be inspected by qualified personnel, using the discharge and lockout procedures required by applicable safety regulations.