How does a voltage event recorder work?

A voltage event recorder continuously calculates the RMS value per half cycle and, when it crosses a configured threshold, stores the event with its start, its duration and its residual or maximum voltage, sometimes with the waveform.

Operating principle

The recorder samples the voltage at high frequency and calculates its RMS value continuously, updating every half cycle or less. It compares each value with thresholds relative to the nominal or reference voltage: a lower one for sags, an upper one for swells and, for interruptions, one close to zero. When the voltage crosses a threshold, the event begins; when it returns inside the threshold, the event ends.

What it stores

  • Time stamp of start and end.
  • Duration of the event.
  • Magnitude: minimum (residual) voltage in a sag or maximum voltage in a swell, per phase.
  • Affected phases and, in many instruments, the waveform and RMS trend around the event.

Features that make it useful

Hysteresis: the exit threshold is slightly different from the entry threshold, so that a voltage oscillating around the threshold does not generate a chain of false events. Circular memory: the instrument continuously stores a few previous cycles, so the record includes what happened before the trigger. Event grouping: a fault followed by reclosures can be recorded as a multiple event or as separate events, depending on the configuration.

What an engineer sees in practice

The result is a list of date- and time-stamped events that can be cross-checked against machine stoppages. The thresholds determine what is seen: if they are very tight you get a huge list of unimportant events, and if they are wide, relevant events are missed. They are defined starting from the tolerance of the most sensitive equipment or from the criterion the results will be evaluated against.

How to interpret the result

An RMS-only record makes it possible to classify depth and duration, but not to see the cause in the waveform. If the instrument does not capture waveforms, there will be no information about transients or phase angle. Measurements are made at energized points and must be carried out by qualified personnel.