Definition
Crest factor is the quotient of a signal’s peak value and its true RMS value. For a perfect sine wave it equals the square root of two, approximately 1.41. A waveform with narrower, higher peaks, such as the current of a rectifier with a capacitor, has a higher factor; a square wave has a factor of one, because its peak equals its RMS value.
How it is measured
- Capture the current with a sensor whose bandwidth and range do not clip the peaks.
- Sample at a high enough rate that the maximum sampled value approaches the true peak.
- Calculate the true RMS value over the window, not the scaled rectified average.
- Divide the absolute maximum value by the RMS value, normally cycle by cycle, and record the maximum or the average.
What can go wrong
- Saturated sensor or low range: clips the peak and reduces the apparent factor.
- Slow sampling: misses the peak and underestimates.
- Instrument that measures only the average: the RMS calculation is wrong with non-sinusoidal waves, and the resulting crest factor has no meaning.
Why it matters
Many devices react to the peak and not to the RMS value: instantaneous-trip circuit breakers, uninterruptible power supplies and generators, which must deliver current pulses instead of a sine wave. A high crest factor, with a load of the same RMS current, places greater demands on backup equipment and can distort the voltage at the source because of the peak drop across the impedance.
How to interpret the result
A crest factor close to the square root of two suggests a nearly sinusoidal current. One that is clearly higher, together with high current harmonic distortion, is consistent with rectifier-type loads. The two figures complement each other: harmonic distortion describes the spectral content, and crest factor describes the peak demand. If sensors are installed in energized panels, this must be done by qualified personnel in accordance with applicable safety regulations.