How Is Power Quality Compliance Verified at the Point of Interconnection?

To verify power quality at the point of interconnection, measure there with a standardized method over a representative period and compare the statistical results with the criteria that apply under the contract, the regulation or the chosen standard.

The answer in four decisions

Verifying compliance is not just measuring: it is comparing a well-made measurement with a clearly identified criterion. Four decisions determine it: where, against what, how and for how long.

Where: the point of interconnection

The criterion applies at the point where the user’s facility connects to the network, or at the point defined by the applicable document. Measuring at an internal point, downstream of a transformer or a long cable, gives other values and does not demonstrate compliance at the point of interconnection.

Against what: the criterion

It may be the Código de Red (the Mexican grid code), a supply contract, a recommended practice such as IEEE 519, or a voltage characteristics standard. Each defines which parameters it evaluates (harmonic distortion, unbalance, flicker, power factor, voltage variations) and whom it holds responsible: some limits apply to the current the user injects and others to the voltage the network must deliver. The limits depend on the edition of the document in force, so they must be consulted directly.

How: measurement method

  • An instrument with a standardized measurement method, such as those defined in IEC 61000-4-30, so that values are comparable.
  • Aggregation intervals and windows consistent with the criterion.
  • Correct transformation ratios and connection, verified before starting.

How long and how to evaluate

The period must be representative of operation, including the most unfavorable load conditions. Evaluation is normally statistical: an instantaneous value is not enough; instead, a percentile or a percentage of time within the limit is calculated over the full period, as defined by the criterion. Events such as sags or interruptions are counted separately.

How to interpret the result

If harmonic voltage exceeds the limit, determine whether the origin is in the network (background distortion already present) or in the facility. Simultaneous current measurement and the direction of harmonic power flow help attribute the contribution. A result outside the criterion does not by itself imply that the user is at fault. Connecting equipment at medium- or high-voltage points is exclusively for qualified personnel, following the applicable regulations.

We do real tests, on video! Watch them on our YouTube channel →