What Does Short Interruption Mean Compared with Sustained Interruption?

The difference between a short interruption and a sustained interruption is the duration of the voltage loss and how service is restored: short ones recover on their own, usually through automatic reclosing; sustained ones require subsequent action.

Functional definition

An interruption is the loss of voltage on all phases at a supply point, with residual voltage close to zero. Classification as short or sustained is by duration, but the exact thresholds are set by the standard or regulation used (some speak of instantaneous, momentary and temporary rather than just short and sustained). So when reading a report, confirm which definition was used to classify each event.

Why each type occurs

Most faults on overhead lines are transient: a branch, an animal, an arc caused by contamination. The circuit breaker opens to clear the fault and, after a short time, an automatic reclosing scheme attempts to re-energize. If the cause has gone, service returns on its own and the user experiences a short interruption. If the fault persists, the breaker stays open and restoration requires repair, manual switching or network reconfiguration: that is a sustained interruption.

Effects in practice

  • In a short interruption, the main problem is the stoppage of processes and equipment without backup, even when power returns within seconds. Continuous processes, electronics and controllers can lose their state.
  • In addition, when voltage returns, the simultaneous re-energization of many loads and transformers can produce high inrush currents and additional trips.
  • In a sustained interruption, the impact depends on whether backup exists (batteries, generator) and how long it can sustain each load.

What an engineer sees in practice

In an event log, a short interruption appears as the voltage falling to almost zero, staying there for an instant and recovering on its own, sometimes with another failed reclosing attempt immediately afterward. A sustained interruption appears as a prolonged loss and usually coincides with notices from the utility or with outages at several nearby facilities.

How to interpret it

Service continuity indices are calculated on sustained interruptions, while short ones are usually counted separately, yet they are often the most damaging for sensitive processes. To decide on suitable backup, it is best to separate the two types: batteries and transfer systems for short interruptions, and backup generation for prolonged ones.