What Is the Negative-Sequence Component in a Three-Phase System?

The negative-sequence component is the part of an unbalanced three-phase system that rotates in the opposite direction to the network; it does not exist in a perfectly balanced system, and in motors it produces heating and oscillating torques.

Basic idea: symmetrical components

An unbalanced three-phase system can be broken down mathematically into three balanced systems: positive, negative and zero sequence. Positive sequence has the normal phase order (the one that turns a motor in its intended direction). Negative sequence has the same magnitude in all three phases but the reverse phase order. Zero sequence consists of three identical phasors in phase with one another, which flow through the neutral or through ground.

When it appears

In an ideal system, voltages and currents have equal magnitudes and a phase shift of one hundred twenty degrees, and only positive sequence exists. Any asymmetry generates negative sequence: unevenly distributed single-phase loads, an open phase, different impedances between phases, capacitor banks with a damaged unit, or large single-phase loads such as furnaces or electric traction.

How it is quantified

The usual indicator of voltage unbalance is the ratio of the negative-sequence magnitude to the positive-sequence magnitude, expressed as a percentage. It can be calculated in the same way for current. This is different from simply comparing the highest and lowest phase voltages, although these methods tend to give results of a similar order.

What effect it has

In an induction machine, negative sequence creates a rotating field in the opposite direction to the rotor. That field induces currents in the rotor at a frequency close to twice line frequency, which heat the rotor and windings, reduce useful torque and produce vibration. A small voltage asymmetry can generate a proportionally much larger current unbalance, because the motor’s negative-sequence impedance is low.

What an engineer sees in practice

You see motors running hotter than expected with no mechanical overload, protection trips for unbalance or phase loss, and different currents between phases. A three-phase analyzer directly shows the unbalance factors and phasors, which tells you whether the origin is the network voltage or the load distribution within the facility.

How to interpret it

If the voltage unbalance is present upstream and also at the service entrance, the origin is external. If it appears only from the load downward, the cause is the load distribution or a fault in a component. Zero sequence, for its part, is what is associated with neutral current and ground faults.