Two definitions, two phenomena
Displacement power factor (DPF) considers only the fundamental component: it is the cosine of the phase angle between voltage and current at line frequency. It is caused by the phase shift typical of inductive loads such as motors and transformers.
True power factor (or total power factor) is total active power divided by total apparent power, calculated with the full RMS values, harmonics included. It answers the question of how much of the current flowing actually produces useful work.
How they relate
In practice, useful active power is delivered by the fundamental voltage and current. Current harmonics increase the RMS value of the current without contributing active power. For this reason, true power factor is the product of the displacement factor and a distortion factor that depends on the current harmonic distortion. If the voltage has little distortion, the distortion factor approaches one divided by the square root of one plus the square of the total harmonic distortion of the current. A direct consequence: true power factor is never greater than displacement power factor.
Where the difference appears
- A purely inductive, linear load: both factors coincide.
- A switch-mode power supply without correction: displacement can be almost one, but true power factor is low because of heavy current distortion.
- A facility with variable frequency drives: displacement is usually high and true power factor lower.
Why it matters for correction
A capacitor bank compensates fundamental reactive power, and therefore improves displacement. It does not reduce harmonic current and, if there is resonance, it can make it worse. If true power factor is low because of distortion, capacitors alone do not solve the problem; filters or reducing distortion at the source are required.
What an engineer sees in practice
Energy meters and analyzers may show one value or the other, and sometimes both. Before comparing readings, you need to know which one the instrument shows and which one the contractual criterion or applicable standard uses. A large difference between the two values is a clear sign of significant harmonic content.