How it forms
When a fault occurs (for example, a phase-to-phase or phase-to-ground short circuit), a current far higher than normal flows through the network impedance to the fault point. That current produces a voltage drop across the source impedance, so all users connected near the supply point see a reduced voltage. It is an impedance divider: the closer the fault and the weaker the source, the deeper the sag.
What causes it
- Network faults: in transmission, in distribution or inside the facility. They are the most frequent cause of deep sags.
- Starting large motors: the starting current is several times the rated current and causes a shallower but longer sag.
- Transformer energization: the initial magnetizing current can be high.
- Loads that change abruptly, such as welders or presses.
How it is described
A sag is characterized mainly by two figures: depth (residual voltage or percentage drop from the reference voltage) and duration. In a fault, duration depends on how long the protection takes to clear it; in a motor start, on how long the motor takes to accelerate. The number of phases affected and the phase-angle jump also matter. Threshold and duration definitions vary between standards, so the reference used should always be stated.
What an engineer sees in practice
The typical symptom is equipment stopping or restarting without conventional lighting giving it away. An event log shows a time-stamped drop in RMS value, which correlates with a drive trip, a contactor dropout or a controller restart. A single-phase fault can appear as a sag on one phase at one point and on two phases at another, because transformers with certain connections change what is seen downstream.
How to interpret it
A sag is not a defect in the equipment that suffers it, but a condition of the network. The useful question is whether the recorded depth and duration exceed what the equipment can tolerate. A brief but deep sag affects electronics and contactors; a shallow, long one affects motors and thermal processes more. To decide the origin (network or your own facility), the direction of the event is also analyzed, a topic covered in another guide.