Insulating Oil Breakdown Test Equipment for Sale in Monterrey

Insulating oil dielectric strength (BDV) tester for laboratories and maintenance of high-voltage equipment. Available in one-, three- and six-cup versions.

Description

The insulating oil dielectric strength tester complies with the ASTM D1816 and ASTM D877 standards. It measures the dielectric strength value of all types of insulating oil. We have three types of oil BDV tester: one-cup, three-cup and six-cup.

Main technical specifications

  • A large-capacity single-chip microcomputer controls the instrument, for stable and reliable operation.
  • It offers several operating options: GB1986, GB2002, IEC156, ASTM D877 and ASTM D1816 (five standard methods) and custom operation, to suit different users.
  • It uses a special single-use glass mold, which prevents oil spills and other interference.
  • Its sampling design at the high-voltage terminal sends the test values directly to the A/D converter. This avoids the errors of analog circuits, and the results are more accurate.
  • It has overcurrent, overvoltage and short-circuit protection, high immunity to interference and good electromagnetic compatibility.
  • It is portable, easy to move and easy to use, both indoors and outdoors.

Technical parameters

Output voltage 0~80kv (or 0-100kv)
THD <1%
Voltage rise rate 0.5~5.0kv/s
Step-up power 1.5 kVA
Measurement accuracy ±2%
Supply voltage AC220V±10%
Power frequency 50Hz±2%
Power 200w
Applicable temperature 0~45℃
Applicable humidity <85% RH
Width*height*depth 410mm*390mm*375mm
Net weight 32 kg

Transformer oil is used in high-voltage equipment as an insulating medium because of its greater electrical strength compared, for example, with gases.

During operation it can break down: it loses the ability to withstand high voltages. A breakdown puts expensive electrical equipment at risk of failure: transformers, oil-filled cables, capacitors, circuit breakers, surge arresters, etc. To prevent it, the breakdown voltage of liquid dielectrics is measured.

Breakdown of liquid dielectrics

This is a complex phenomenon that is still being researched. One of the main theories is this: if high voltage is applied to the oil for a long time and it contains inclusions, the inclusions become polarized and form chains along the field lines. The chains become a conduit for electric current. The current heats the liquid next to the channel until it boils, and breakdown occurs through the gas channel that forms.

In highly refined oils, breakdown can be due to impact ionization of the molecules. After a breakdown, the electrical insulating properties of the oil are restored, but its quality usually deteriorates noticeably.

Transformer oil breakdown voltage

The dielectric properties of the oil are verified by sampling and subsequent analysis: breakdown voltage, dielectric loss tangent, dielectric constant, etc.

Breakdown voltage is the minimum applied voltage at which a conductive channel forms in the dielectric. It is generally measured in kilovolts.

Dielectric strength is also used: physically, the voltage that must be applied to a sample to make it break down, divided by the thickness of the sample. It is measured in kilovolts per millimeter.

What factors affect the breakdown voltage of transformer oil?

Breakdown voltage is a very sensitive parameter in transformer oil. It is influenced by the following factors, among others:

  • Contamination with mechanical impurities and moisture. The dirtier the oil, the lower its breakdown voltage.
  • Viscosity. As the oil’s viscosity decreases, the breakdown voltage also decreases.
  • Temperature. As temperature increases, the breakdown voltage decreases. With impulse voltage this relationship is weak. In highly purified oils, the temperature dependence is complex.
  • Pressure. As pressure increases, the breakdown voltage increases, which is explained by the increase in pressure in the gas bubbles. The dependence is more marked in technically pure oil.
  • Prolonged exposure to voltage. The longer the voltage is applied to the oil, the lower the breakdown voltage. The dependence weakens in oils with a deeper degree of purification.
  • Electrode shape, area and spacing. Different electrode shapes create fields with different degrees of non-uniformity; the higher the non-uniformity coefficient, the lower the breakdown voltage. As electrode area increases, the breakdown voltage decreases, and as electrode spacing increases, it increases.