Conductivity, dissipation factor and Q factor testing

At Electrónica Monterrey we test and analyze material conductivity, dissipation factor and Q factor. For engineers evaluating materials and electrical insulation.

Conductivity, dissipation factor and Q factor testing

Electrical conductivity

Electrical conductivity (symbol σ) is a measure of the ability of a material or substance to let electric current pass through it. It depends on the atomic and molecular structure of the material. Metals are good conductors because their structure has many weakly bound electrons, which allows them to move. It also depends on other physical factors of the material and on temperature.

Conductivity is the inverse of resistivity (symbol ρ). Its unit is S/m (siemens per meter) or Ω−1·m−1. Usually, the magnitude of conductivity is the proportionality between the electric field and the conduction current density.

Electrical conductivity and resistivity

One of the subatomic particles of an atom is the electron. Electrons carry a negative electrostatic charge and under certain conditions can pass from one atom to another. The direction of movement between atoms is random unless a force makes the electrons move in one direction. This directional movement of electrons due to an electromotive force is what is known as electricity.

Measurement in % IACS

Electrical conductivity is a measure of how well a material accommodates the movement of an electric charge. It is the ratio of current density to electric field strength. Its SI derived unit is the siemens per meter, but values are often reported as a percentage IACS. IACS is an acronym for International Annealed Copper Standard, established by the International Electrochemical Standard of 1913.

The conductivity of annealed copper (5.8001 x 107S/m) is defined as 100% IACS at 20 °C. All other values are related to this conductivity. For example, iron, with a value of 1.04 x 107 S/m, has a conductivity of approximately 18% of that of annealed copper and is reported as 18% IACS. Commercially pure copper products today often have values above 100% IACS, because processing techniques have improved since 1913 and more impurities can now be removed from the metal.

Values in siemens/meter are converted to % IACS by multiplying them by 1.7241 x10-6. When values are reported in microsiemens/centimeter, they are multiplied by 172.41.

Conductivity values are affected by the chemical composition of substances and by the stress state of crystal structures. That is why they are used to measure water purity, sort materials, verify the proper heat treatment of metals and inspect for heat damage in some materials.

Electrical resistivity

Electrical resistivity is the reciprocal of conductivity. It is the opposition of a body or substance to the flow of electric current, which results in a conversion of electrical energy into heat, light or other forms of energy. Resistance depends on the type of material. Materials with low resistivity are good conductors and those with high resistivity are good insulators.

Insulating materials play an important role in all electrical equipment. They must isolate the energized parts of an apparatus from its other parts that operate at different voltages or are at ground potential. Failure to do so has serious consequences, including failure of the apparatus itself. In oil-filled apparatus such as transformers, dielectric failures can cause fires, explosions, damage to surrounding equipment and the end of service life.

Several electrical tests for off-line equipment evaluate insulation condition:

  • DC insulation resistance test.
  • Power factor/dissipation factor (PF/DF) and capacitance.
  • Dielectric response methods, such as dielectric frequency response (DFR).

Each test serves a unique function with respect to transformer testing needs, so it is worth understanding them all. The electric power industry has relied on power factor/dissipation factor and capacitance for nearly a century to evaluate insulation. These tests detect localized defects in multilayer insulation systems and gained popularity in the early twentieth century, when condenser-type bushings were becoming widespread. Manufacturing problems in these bushings were not consistently identified with DC insulation resistance, and manufacturers preferred power factor/dissipation factor and capacitance.

Power factor/dissipation factor and capacitance are measured simultaneously in the same test. Each provides different information about the condition of an insulation system.

Q factor

The Q factor, also called the quality factor or selectivity factor, measures the ratio of the reactive energy a system stores to the energy it dissipates during a complete signal cycle. A high Q factor indicates a low rate of energy loss relative to the energy stored by the resonator. It is an important parameter for oscillators, filters and other tuned circuits, because it measures how sharp their resonance is.

Resonant systems respond to one particular frequency, called the natural frequency, eigenfrequency or resonant frequency, much more than to the others. The range of frequencies to which the system responds significantly is the bandwidth, and the center frequency is the electrical resonant frequency.

The quality factor is also defined for components, in particular varactors and crystals.

The quality factor of passive circuits made up of resistors, coils and capacitors is low, below 100, mainly because of the resistivity of the coil wire, since high inductance values require great lengths of wire. Active circuits that work as inductance or capacitance multipliers can improve Q.

Speak with the engineer at Electrónica Monterrey to define the test you need.